Fished new wire for the first time! - eviltoast

I posted on here the other day about some suspicious 240v cable and followed the recommendations to replace it. I was already leaning that way but was kind of hoping to be told I was overthinking it. But you all confirmed what I thought. I ran close to 25’ of 10/2 cable from the second story to the basement. Nothing is wired yet because it is late and I don’t want to turn on the main breaker.

My step dad let me borrow a 50’ fishing tape and 10’ endoscope which were really helpful. I did not have to cut any walls!

  • AspieEgg@lemmy.blahaj.zone
    link
    fedilink
    arrow-up
    9
    ·
    10 months ago

    Since you went with 10/2 for a 240v outlet that means your cable will have two hots and a single ground. But the cable you bought will have a black, white and bare/green wire. Make sure that you wrap both ends of the white conductor with red electrical tape to indicate that it is also a hot wire. White normally indicates a neutral, but since you won’t have a neutral wire in this cable, it’s important to mark it. Otherwise someone else may work on this outlet in the future, see a white wire, assume it’s a neutral, wire something up with it as a neutral, and give themselves a pretty bad shock.

    • Uprise42@kbin.socialOP
      link
      fedilink
      arrow-up
      3
      ·
      10 months ago

      Yup, I already have the electrical tape to mark it. Though I was told I could mark it red or black and both are universal markings for hot wire. Is that wrong? It doesn’t matter here because I have red tape but for future reference it would be good to know

      • AspieEgg@lemmy.blahaj.zone
        link
        fedilink
        arrow-up
        3
        ·
        10 months ago

        You can mark it either red or black, but you already have one black wire, so it would be best to mark it red, just to differentiate it.

  • Switorik@lemmy.zip
    link
    fedilink
    arrow-up
    6
    ·
    10 months ago

    I’m an electrician. It is too late but for future reference all new work must be done up to code. An electric dryer requires 10/3 on a 30A breaker that is listed for the panel.

    While this is not code compliant, 10/2 will still work but requires you to install the jumper from the neutral to the ground inside the dryer itself.

    • Uprise42@kbin.socialOP
      link
      fedilink
      arrow-up
      2
      ·
      10 months ago

      Ya, I know I need to jump the ground when wiring to power cable for the dryer. I was going to do 10/3 since I had the money for it, but lowes and Home Depot were both sold out when I went to pick it up. Whirlpool told me 10/2 would work so I just went with that in the effort of saving time. New dryer is delivered Tuesday so I want the wiring done before then. The 30a double pole breaker was easy though. Probably the least questionable part of this process